| Water
Dept. - Tap
Specifications
Frequently
Asked Questions || Services
|| Water
Home Page ||
Water
Rates || General
Info
||
City of
Kirkwood Water Department
Specifications
for the Construction of
Water Mains and Fire Services
GENERAL
These Specifications describe
requirements for the installation of water mains and fire
services. If any discrepancy occurs, these Specifications shall
take precedence over any Drawings.
All materials and methods of
construction shall meet the requirements of the City of Kirkwood
Water Department. Unless specified herein, installation shall
comply with the most recent revision of American Water Works
Association Standard C600.
All references to Standard
Specifications shall be considered to be the most recent
revision of such Standard Specifications in effect at the time
of project initiation.
The verification of the location of all
underground facilities, structures and utilities shall be the
responsibility of the Contractor and, if damaged, shall be
repaired by the Contractor at his own expense.
These Specifications are subject to
revision by the Water Department without notice.
MATERIALS
OF CONSTRUCTION
All materials
shall be new, unused, undamaged and clean when installed.
Pipe
Pipe shall be ductile iron,
cement-lined, Class 52, push-on joints meeting AWWA standard
C151. Fire services shall be appropriately sized by the
developer’s or contractor’s engineer. Joints shall be
push-on type rubber gasket in accordance with AWWA standard
C111.
Gaskets
Gaskets shall properly match bell
configuration.
Polyethylene
Encasement
Polyethylene encasement shall be in
tube form, shall have natural (clear) color, and shall have a
minimum thickness of 12 mils. Flat tube width shall correspond
to the diameter of pipe being laid. Polyethylene sheets shall be
used for odd shaped appurtenances. Black-colored encasement
shall not be permitted.
Fittings
All fittings, which include bends, tees, crosses, plugs and caps, shall be
ductile iron, slip-on connections in accordance with AWWA
standard C110 or C153, and shall be cement-lined in accordance
with AWWA standard C104.
Valves
Valves shall
be ductile iron body, resilient wedge gate, non-rising stem
type, O-ring seals, and slip-on connections (tapping valves
shall be flange x mj). They shall be American Flow Control
Series 2500, Kennedy Ken-Seal II, or Mueller Cat. No. A-2360.
The valves shall be suitable for cold water, non-shock,
bi-directional flow operation, and working pressure of 200 PSI.
They shall be of such design as to maintain the full area of the
pipe through the valve when open and shall be designed to take
full pressure on either face. They shall be opened by turning
counter-clockwise and shall have two-inch square cast iron
operating nuts with an arrow cast in the nut indicating the
direction of opening. Valve shall have Type 304 stainless steel
bonnet bolts and nuts and type 304 stainless steel O-ring gland
bolts and nuts. Valves shall have the manufacturer’s name or
initials and the pressure rating cast on the body.
Valve
Boxes
Valve boxes shall be provided for all
valves installed. They shall have suitable bases to fit around
the valve bodies without bearing on them. Barrels shall be
telescopic for adjustment and shall have a minimum inside
diameter of five inches. They shall be designed for the depth of
trench specified. The top section shall have a flange for
holding it in position. Covers shall be recessed flush with the
top and marked “water” in raised letters. Valve boxes shall
weigh not less than 90 lbs.
Fire
Hydrants
Fire hydrants shall be 5-1/4”
diameter valve opening, 3-way (one 4 ½” diameter steamer
nozzle and two 2 ½“ diameter hose nozzles), national standard
thread, six-inch diameter slip-on shoe with lugs, open counter
clockwise, 1½” operating nut, and shall be American Darling
B-84-B or Kennedy K81D. Bury depth of hydrants shall be such
that the top of the traffic flange shall be positioned no
less than two inches and no more than six inches above finished
grade. The installation of hydrant extensions is not permitted.
Tapping
Sleeves and Valves
Taps of four inch and larger diameter
shall consist of a stainless steel tapping sleeve. The tapping
sleeve shall be constructed entirely of stainless steel.
Carbon steel or ductile iron flanges are not permitted. Approved
sleeves include Ford FTSS, Mueller H-304, Power Seal 3490, Romac
SST III, or Smith-Blair 665. The tapping valve shall comply with
the requirements previously described in the valve section, with
the exception of tapping valves shall be flange x mj. Tapping
valves shall be American Flow Control series 2500, Kennedy
Ken-Seal II, or Mueller A-2360.
Corporation
Stops
Corporation stops shall be a minimum
diameter of one inch and shall be sized according to the service
line diameter if the service line diameter is larger than one
inch. Corporation stops shall be ground key AWWA taper “CC”
thread by copper flare eighth bend connection. One-inch
corporation stops shall include dielectric nylon insulators,
shall be Mueller N-35000 and shall include Mueller H-15063
eighth bend couplings. 1½ and 2 inch corporation stops shall be
Mueller H-15020.
Service
Saddles
Service saddles (used for 1 ½ and 2
inch corporation stops) shall be brass body with double
flattened silicone bronze straps. Saddles shall be Ford 202B or
Mueller BR2B.
Curb
Stop Valves
Curb stop valves shall be flare
connections, and shall not be compression type.
Service
Line Couplings
Service line couplings shall connect to
both new and existing copper service lines using flare
connections only. Compression type end connections are allowed
for connection only to existing lead or steel service lines.
MATERIAL
STORAGE
All materials shall be stored in a safe
and secure manner and in such a way as to prevent damage to the
materials. Pipes, hydrants valves and fittings may be laid
directly on the ground, but in such a way as to prevent water
from accumulating inside these materials. Gaskets and
polyethylene film shall be protected from direct sunlight.
Gaskets shall not be allowed to come into contact with petroleum
products.
If water mains or fire hydrants are
stacked, the bottom tier of pipes/hydrants shall not be laid
directly on the ground, but shall be held off the ground and
supported by timbers. Timbers shall also be installed between
each tier, preventing contact between tiers.
TRENCH
EXCAVATION AND BACKFILL
The trench shall be excavated to a
depth of at least six inches below the bottom of the pipe. The
trench shall be at least twelve inches wider than the outside
diameter of the pipe. The pipe shall be laid in the center of
the trench so a minimum distance of six inches is maintained
between the outside of the pipe and each trench wall.
Prior to placing the pipe, at least six
inches of one-inch clean, crushed limestone bedding shall be
placed and leveled in the bottom of the trench. The bedding
shall be true and even, and shall provide a uniform and
continuous bearing and support for the pipe, except that it will
be permissible to disturb the backfill material near the center
of each length of pipe to permit the withdrawal of pipe slings
and other lifting equipment. All water main and appurtenances
shall be inspected and approved by a Water Department
representative prior to covering the new pipe. Any piping or
appurtenances that are covered or otherwise hidden from view
prior to receiving approval from the Water Department shall be
completely uncovered in order to permit a thorough inspection.
After installation of the pipe is
complete, one-inch clean crushed limestone shall be placed
around each side of the pipe (six-inch minimum width on each
side), and over the top of the pipe (minimum thickness of twelve
inches).
Trench backfill from the top of the
granular bedding to the level of existing grade adjacent to the
trench shall be in accordance with the policies and procedures
established by the City’s Public Works Department. Suitable
native material previously excavated from trench and/or
supplemental borrow material if the trench is not to be located
beneath pavement of any kind. Backfill shall be placed in layers
of thickness within the compacting ability of the equipment
used. Compaction of the trench backfill shall be performed at
the proper moisture content of the backfill material to achieve
the desired results, and accomplished without inundation.
Under road pavements, sidewalks,
driveways and parking lots, one-inch clean backfill shall be
compacted to 95 percent of maximum dry density (see “Pipe
Bedding Detail Under Pavement” on drawings). In other areas,
backfill shall be compacted to the degree necessary to prevent
significant future settlement.
INSTALLATION
Pipe
Pipe and fitting joints shall not be
deflected more than two degrees during assembly and shall not
have a deflection of more than four degrees after assembly.
Carefully examine each pipe immediately
prior to installation. All visible foreign material shall be
removed from the pipe immediately prior to its installation. If
necessary, the Contractor shall rinse the interior surface of
the pipe. Install pipelines to grades and alignment indicated.
Provide proper facilities for lowering sections of pipe into
trenches. Pipe shall not be rolled or dropped into the trench.
Immediately prior to installing each pipe section, the
previously installed section of pipe must be inspected to insure
that no foreign material has entered the pipe since its
installation. If any foreign material is discovered in the
previously installed section of pipe, it shall be removed prior
to installing the next pipe section. Polyethylene encasement
shall be installed in accordance with AWWA C105. Lubricant shall
be applied according to the manufacturer’s instructions and
shall be in accordance with AWWA C111. Under no circumstances
shall pipe be laid in water and no pipe shall be laid when
trench conditions or weather are unsuitable for such work. Full
responsibility for diversion of drainage and for dewatering of
trenches during construction shall be borne by the Contractor.
At times when pipe laying is not in progress, watertight plugs
shall close the open ends of the pipe. Foreign material shall be
prevented from entering the pipe during and after installation.
Mains shall not be tapped for service
line connections prior to the installation, disinfection and
pressure testing of the water main, unless a tap is needed for
flushing and pressure testing purposes.
Water mains shall have no less than 42
inches and no more than 48 inches of cover after finished
grading. Exceptions
to this rule may be made by the Water Department to provide
necessary clearance from sanitary and storm sewers, and to
accommodate conflicts with other utilities. Such approval must
be obtained from the Water Department prior to any installation
that deviates from these specifications.
If the existing grade elevation in the
vicinity of the water main installation is to be altered,
finished grade elevation stakes shall be set by the
developer’s or contractor’s engineer prior to the
installation of water main. The stakes shall be set within 10
feet of the water main trench and shall be placed at least every
50 feet along the water main route.
If,
after finished grading is complete, any portion of the water
main has more than 48 or less than 42 inches of cover, and this
installation outside the required limitations did not receive
prior approval from the Water Department, the developer shall
relocate that portion of water main to the required depth at his
expense.
Restrained
Joint Gaskets
At every location a restrained joint
gasket is installed, the Contractor shall wrap indicator tape
around the joint. The
tape shall indicate the presence of a restrained joint gasket
within that joint.
Polyethylene
Encasement
Installation of polyethylene encasement
shall be in accordance with AWWA standard C105.
Polyethylene shall also encase socket
clamps, threaded rod, washers and nuts.
Encasement shall be secured with duct tape.
All pipes, valves, fittings, tie rods,
clamps, and appurtenances shall be protected with clear
polyethylene encasement. The encasement shall prevent contact
between the pipe and the surrounding backfill and bedding
material.
Bends
All bends
shall be installed with thrust blocks adequately sized for the
degree of bend, diameter of bend, and anticipated system
pressure. In lieu of thrust blocks, the contractor may use joint
restraint gaskets to restrain the bend to the pipe. If the
contractor chooses to use restrained joint gaskets in lieu of
thrust blocks, additional joint restraint gaskets will be
required in each direction from the bend. The contractor may
also choose to pour a “dead man” concrete thrust block
around the first pipe joint in both directions from the bend.
These two joints within the concrete “dead man” thrust
blocks shall also contain joint restraint gaskets.
Fittings
Plugs shall be restrained in bells of
pipe and fittings by setscrews and concrete thrust blocks. Caps
shall be restrained to pipe with two sets of socket clamps and
threaded rod, and by concrete thrust blocks.
Valves
Valves shall
be installed in a horizontal position with the operating nut
vertical.
Valve
Boxes
A valve box shall be installed above
each valve. Valve boxes shall be installed such that the top of
the box is no more than ¼ inch below street pavement, flush
with sidewalk pavement, or when in lawns, flush with the dirt
surface. Valve
boxes shall never pose a trip hazard or a potential threat of
damage to lawn mowers.
Tapping
Sleeves and Valves
Immediately prior to installation, the
following surfaces shall be sprayed with household bleach until
thoroughly wet:
1)
The
interior of the tapping sleeve branch
2)
The
interior of the tapping valve, including both sides of the gate.
3)
The
pilot drill bit and the shell cutter of the tap machine
Corporation
Stops
Corporation stops shall be installed
only after the water main has been installed and has been placed
into service. They shall be installed on the water main at 10
o’clock or two o’clock positions on the water main diameter.
One-inch diameter corporation stops shall be direct tapped to
the water main. 1 ½ and 2-inch diameter corporation stops shall
be attached to the water main with service saddles. Dielectric
nylon service insulators shall be installed between two flare
copper adapters.
Connections between the service line
and the corporation stop shall be supported with blocking, the
uppermost layer of blocking being of wood.
Curb
Boxes
Curb boxes shall be installed
vertically and shall be perfectly centered over the curb stop
valve.
Curb boxes shall be installed such that
the top of the box is flush with the dirt surface. Curb
boxes shall never pose a trip hazard or a potential threat of
damage to lawn mowers.
Service
Line Transfers
When the Contractor connects any
existing water service to the new tap, he must coordinate
with the Water Department personnel to enable Department
personnel to remove the water meter from the service line before
the new corporation stop is turned on. Once the meter is
removed, the Contractor shall turn the corporation stop fully
on. Department personnel will flush the service line into the
meter box and replace the meter. If the Contractor fails to
properly coordinate this process with Department personnel, and
failure to do so causes plugging of the resident’s plumbing
fixtures, the contractor shall be responsible for cleaning
and/or replacing the resident’s fixtures.
Pipe
Clamps and Rods
In-line valves, fittings, bends or tees
need not be anchored to the “run” pipe with threaded rod.
Threaded rod, rod nuts and washers, if used, shall be thoroughly
coated with a bituminous coal tar spray after installation.
Threaded rods and socket clamps, when
used, shall be installed prior to placing concrete thrust
blocks.
FIRE
SERVICE VAULTS
Vaults shall be adequately sized to
contain: 1) pipe tee that splits the fire and domestic services; 2) double or single detector check valve; including OS&Y
valves on both ends; 3) detector meter, valves, and double or
single check valve on detector meter bypass; 4) collapsible
fitting; 5) domestic
meter (if 1 ½” or larger), valves at both ends, bypass line;
6) any and all appurtenances required by the Fire Department.
Domestic water meters 1” diameter or
smaller shall not be installed within the main fire service
vault, but shall be installed in a standard residential meter
box immediately next to the main fire service vault.
Backflow
Preventors/Detector Meters
Backflow preventors for fire services
may be installed in the fire service vault. Backflow preventors
installed in the fire service vault shall be double detector
check valves. If the backflow preventor is installed inside the
building, a single detector check valve shall be installed in
the fire service vault. Single detector check valves shall not
be installed in pyramid vaults, but shall be installed in vaults
large enough to contain the detector check valve, both OS&Y
valves, and collapsible fitting. Detector meters on both double
and single detector check valves shall be purchased from the
City and installed by the contractor.
Both double and single detector check
valves installed in fire service vaults shall have installed
OS&Y valves at both ends. A collapsible fitting, assembled
using two flange X plain end pipes, and a mechanical joint
coupling connecting the two plain ends, with approx. a 1” gap
between the plain ends, shall be installed by the contractor.
SEPARATION
OF WATER MAINS, SANITARY AND STORM SEWERS
Water mains installed parallel to any
sanitary sewer pipe line shall be installed with no less than 10
feet of horizontal separation between the outside of the water
main and the outside of the sewer. Where 10 feet of separation
is not possible, the entire water main located 10 feet or less
from the sanitary sewer shall be encased in concrete.
Water mains crossing sanitary sewer
pipelines shall be installed to provide no less than 18 inches
of vertical clearance between the two pipelines.
At crossings in which water main will already have at
least 18 inches of clearance from the sanitary sewer, a full
length of water main shall be installed so both joints will be
as far from the sewer as possible.
No water main shall be located closer
than 10 feet to any part of a sanitary sewer manhole.
Where 10 feet of separation is not possible, the entire
water main located 10 feet or less from the sanitary manhole
shall be encased in concrete.
Water mains crossing storm sewers shall
be installed to provide a minimum vertical clear distance of six
inches between the outside of the water main and the outside of
the storm sewer.
If necessary, the Contractor shall
install four 45° bends
to achieve the minimum clearance between the water main and
sanitary or storm sewers.
FIRE
HYDRANT INSTALLATION
Hydrants shall stand plumb with pumper
nozzles facing the curb. They shall be installed so the top of
the traffic flange is no less than two inches and no more than
six inches above finished grade. The installation of hydrant
extensions is not permitted. Hydrant supply branches shall be
controlled by an independent resilient seat gate valve.
Valves shall be slip-on and shall be
restrained to tees using restrained joint gaskets or threaded
rods, to allow shut-off when the hydrant is to be removed.
Hydrants shall be restrained to valves using restrained
joint gaskets or threaded rods. Regardless of which restraint
system is used, thrust blocks shall always be poured between the
back of the hydrant bowl and undisturbed earth.
Hydrants shall be installed between the
street curb and the sidewalk, 24-32 inches from back of street
curb. Once final landscaping has been completed, the Contractor
shall remove all nozzle cap chains, thoroughly clean and remove
all rust from the hydrant, and paint the hydrant with a gloss
finish oil-based alkyd coating. The color shall be safety
yellow.
THRUST
BLOCKS
Thrust blocks shall be installed in
accordance with the details and table shown on the Miscellaneous
Details Sheet.
Concrete thrust blocks shall be
installed at all fittings, bends, hydrants and changes in
alignment of the water main to take the thrust of the water
pressure. Thrust blocks shall have a compressive strength of not
less than 2000 psi after 28 days.
Blocks shall distribute the thrust
forces to the soil structure in such a manner that joint
separation will not occur. The blocks shall be so located as to
contain the resultant thrust force in such a way that the pipe
and fitting joints will be accessible for repair. Final approval
of thrust block sizing and installation shall be at the
discretion of the Water Department.
The Contractor may use restrained joint
gaskets as an alternative to thrust blocks (with the exception
of fire hydrants) upon prior approval by the Kirkwood Water
Department. The number and location of restrained joints upstream and
downstream of the point of thrust must be selected by the
Contractor according to the water pressure and soil conditions,
and shall be subject to approval by the Water Department.
INSPECTIONS
All piping and appurtenance
installation shall be inspected and approved by Water Department
personnel prior to backfill. Any portion of work that is
backfilled prior to inspection shall be uncovered at the
Contractor’s expense to enable Water Department personnel to
thoroughly and adequately inspect all work. The Contractor shall
provide sufficient access and reasonable aid to the inspector to
allow for thorough inspections of the work.
DISINFECTION
All piping shall be disinfected in
accordance with AWWA standard C651 prior to being placed into
service. Disinfection shall be by the granular method. Calcium
hypochlorite granules (HTH) shall be placed inside the upstream
end of the first section of pipe, and every 500 feet thereafter.
In addition, granules shall be placed inside the upstream end of
each branch main, and every 500 feet thereafter. The quantity of
granules placed shall correspond to Table 1 of the AWWA
Specification. Eight-inch diameter main receives a minimum of
seven ounces of granules at each application point.
Following installation, the main shall
be filled and flushed. The filling and flushing procedures shall
be performed by Water Department personnel only. The contractor
is not allowed to fill or flush the main.
If a fire hydrant does not exist on the new main, the
Contractor shall, at his expense, install a one-inch minimum
diameter corporation stop in the top of the main at the highest
elevation for flushing and sampling purposes. Following
acceptable bacteria test results, the contractor shall remove
the tap and replace it with a bronze plug. Water Department
personnel shall collect all bacteria samples and shall conduct
all bacteria analyses. If the contractor does not want bacteria
samples collected from a fire hydrant, he may, at his expense,
install a tap for sampling purposes. Following acceptable
bacteria test results, the contractor shall remove the tap and
replace it with a bronze plug. If bacteria analyses fail to
produce acceptable results, Water Department personnel will
repeat the flushing, sampling and bacterial analyses procedure a
second and, if necessary, a third time.
If, after the third attempt, water
quality does not meet requirements, the Contractor, at his
expense, shall fill the entire length of water main with a
solution of water containing no less than 50 parts per million
available chlorine. After 24 hours contact time, the Water
Department will perform another flushing, sampling and bacterial
analyses procedure. This process will be repeated until results
are acceptable.
HYDROSTATIC
TESTING
Unless specified herein, all
underground piping shall be tested hydrostatically by the
contractor in accordance with AWWA standard C600. Test pressure
shall not be less than 1.5 times the working pressure at the
point of testing, or not less than 100 PSI, whichever is
greater. The duration of the test shall be a minimum of two
hours. Test pressure shall not vary by more than +/- 5 PSI for
the test duration. The
Contractor may use a fire hydrant on the new main to conduct the
pressure test, or may install a corporation stop for a test
connection.
Leakage is defined as that quantity of
makeup water that must be supplied to maintain, within 5 psi,
the specified test pressure for the entire two-hour test
duration. Pressure drops shall not be used to measure leakage.
If the new main does not pass the pressure test and a leak
cannot be found, it will be the contractor’s responsibility to
disconnect the new main from the existing main, cap the new main
at those connections, and perform another pressure test to
eliminate the possibility of leakage through the valves at the
connections to the existing mains.
Maximum allowable leakage shall be in
conformance with AWWA standard C600, Table 6A. All visible leaks
are to be repaired, regardless of the amount of leakage. Testing
and replacement of any section of pipe, valve or fitting shall
be performed by the Contractor at his expense.
When a hydrant is not being installed
along the new water main, the Contractor shall install a
one-inch diameter corporation stop at the highest elevation on
the new main and on top of the pipe for flushing, sampling, and
pressure testing. Once
the pressure test is completed and approved, the contractor
shall remove the corporation stop and install a brass plug.
Hydrostatic testing shall be observed
by and approved by a Water Department representative.
FINAL
CONNECTIONS
If the Contractor connects the new main
to an existing main after the new main has successfully
passed the bacteriological testing, the interior of all new
materials used to make the final connection shall be thoroughly
sprayed with household bleach immediately prior to their
installation. If the Contractor connects the new main to an
existing main after the new main has successfully passed
the pressure test, water to all portions of the new connection(s)
must be turned on and the new connection(s) pressurized. These
connections shall be left under full system pressure for a
minimum of twenty-four (24) hours, at which time they will be
inspected for leaks by Water Department personnel.
SHUTDOWNS
OF EXISTING MAINS
When water service to existing
customers must be interrupted to sections of mains to enable the
contractor to disconnect and abandon water mains, or for any
other scheduled reason, the contractor shall provide the Water
Department with a 24-hour minimum notice. Water Department
personnel will notify those customers to be affected by door
hanger notices on the day prior to the scheduled shutdown.
Scheduled shutdowns shall not begin prior to 9:00am or extend
beyond 3:00pm. If the contractor encounters unforeseen
difficulties, he must continue working until service has been
restored. When transferring individual single-family residential
services to the new main, the contractor shall be responsible
for delivering notice to the occupant. Twenty-four hour notice
and door hangers are not required for individual single-family
residential service transfers.
SITE
SAFETY AND PROPERTY PROTECTION
The Contractor shall, at all times,
conduct his operations in such a manner and employ all
reasonable means to prevent damage to public and private
property. Any damage to public or private property as a result
of the contractor’s failure to comply with any portion of
these specifications or federal, state or local regulations
shall be repaired at the contractor’s expense.
The contractor shall keep all utilities
marked while excavating in their vicinity.
The Contractor shall, at all times,
comply with the City’s Public Works Department’s Excavation,
Restoration and Land Disturbance Requirements.
Trees, shrubs, miscellaneous plantings,
planter areas, ornamental structures, retaining walls and all
other structures shall be protected from damage during
construction, and shall be supported or temporarily relocated if
necessary at the Contractor’s expense. Items shown in the
drawings or plans to be removed and reinstalled shall be
protected by the Contractor while in storage.
Support and protection of all
structures, both above ground and below, and within the
immediate vicinity of the work, shall be the Contractor’s
responsibility at his expense.
TRAFFIC
CONTROL
Traffic control shall comply with all
applicable Federal, State and Local regulations. Adequate
barricades, warning signs and lights shall be installed and
maintained on a continuous basis by the Contractor. These safety
devices shall be adequate to advise, warn and protect the public
from any hazards arising from or otherwise associated with the
Contractor’s work. The Contractor shall, at all times, comply
with the City’s Public Works Department’s Excavation,
Restoration and Land Disturbance Requirements.
SITE
CLEANLINESS
The contractor shall maintain the
construction site in a neat and orderly appearance. Streets,
sidewalks, parking lots and curbs shall be shoveled and swept
clean of mud, dirt and debris on a daily basis and washed down
as necessary. All trash and waste materials shall be removed
from the site on a daily basis. Any excavated material that is
not to be reused shall be removed from the site immediately. Any
excavated material that is to be reused may be stored on site,
but shall not be stored in the street or on a sidewalk. Stored
excavated material shall be covered with plastic at all times to
prevent runoff from precipitation. Site cleanliness and the
storage of materials shall, at all times, comply with the
City’s Public Works Department’s Excavation, Restoration and
Land Disturbance Requirements.
PROPERTY
RESTORATION
The contractor shall restore all
disturbed areas as nearly as practicable to their original
condition.
Disturbed grass areas include not only
those areas disturbed for excavation and installation of pipe
and appurtenances, but also those areas disturbed by storage of
materials, and operation and storage of equipment.
Any sod installed after June 15 that
does not indicate substantial growth in the fall shall be
replaced by the Contractor at his expense.
All street, driveway and sidewalk
pavement repair and replacement, and lawn repair shall, at all
times, comply with the City’s Public Works Department’s
Excavation, Restoration and Land Disturbance Requirements.
WARRANTY
The contractor shall guarantee
materials and workmanship for a period of not less than one year
from the time the main is placed into service. Any leaks that
develop within the first year shall be repaired by the
developer/contractor. The contractor is responsible for
deterioration or settlement of restored areas for a period of
one year after completion of all restorations.
Specifications last revised August 2003
|